Massachusetts Spec Lab
Boston, Massachusetts
MA779 – Although not established as basis-of-design, we leveraged our relationship with the mechanical engineer and the mechanical contractor to provide a solution that came in on-time and on-budget. The construction quality, timely delivery, and engineering support provided by Buckley and SolutionAir gave the end user the confidence to proceed with a second unit to serve future lab expansion within the building.
Paul Buckley
overview
Project Type: Lab/Health Care
SolutionAir Rep.: Buckley Associates Inc.
Product(s): 9,800 CFM Drum and Tube Gas Furnace with DX Cooling and Hot Gas Reheat
Product Model ID: MA779
Performance
Airflow: 9800 CFM
Minimum Airflow: 4900 CFM
Filters: 2″ MERV 8 pre-filter, 4″ MERV 13 final.
Fans: Plenum Backward Curved with VFD
Furnace: 80% efficient Drum and Tube, 800 kBTU/h output, 15:1 turndown
Evaporative Coil: 6 row, 10 FPI, 585.6 MBH
Hot Gas Reheat Coil: 178 MBH
ACCU: R-410A Digital Compressor
Feature: Empty coil section with drain pan for future humidifier grid